Page 1 --- Showing records 1 - 6 (out of 6)
| Item # |
Description |
Price |
Cart |
OFF-LINE SWITCHING POWER SUPPL
Model AL400ULXB power supply/charger converts a 115VAC 60Hz input,
to 12VDC @ 4 amp or 24VDC @ 3 amp of continuous supply current output.
Class 2 Rated power limited output.
Agency Listings
UL Recognized Component for Access Control Systems (UL294),
Power Supplies for use with Burglar Alarm Systems (UL603),
Hospital Signaling and Nurse Call Equipment (UL1069),
Power Supplies for Fire Protective Signaling Systems (UL1481)
File# S4707.NFPA 72 Compliant
Features/Specifications
12VDC or 24VDC selectable output
4 amp @ 12VDC or 3 amp @ 24VDC of continuous supply current output.
Class 2 Rated Power limited output.115VAC 60Hz, 1.45 amp input.
Filtered and electronically regulated outputs
Short circuit and thermal overload protection
Built-in charger for sealed lead acid or gel type battery backup
Maximum charge current .7 amp.Zero voltage drop upon transfer to battery backup
AC input and DC output LED indicators.
AC fail supervision (form "C" contact rated @ 1 amp 28VDC)
Low battery and battery presence supervision
(form "C" contact rated @ 1 amp 28VDC)
Lifetime Warranty
Board
Dimensions (approximate):
4.6"W x 7.5"L x 2.7"H
You must be logged in to request more information about products.
Login or Call
for Pricing.
Special Order Item.
ACCESS POWER CONTROLLER w/POWE
Model AL600ULACM converts a 115VAC 60Hz input into eight (8) independently controlled
12VDC or 24VDC non power limited fuse protected Fail-Safe and/or Fail-Secure outputs with
a total of 6 amp continuous supply current.
The fire alarm disconnect feature enables emergency egress in the event the fire alarm system is
activated. It is individually selectable for any or all of the eight (8) outputs. Model AL600ULACMCB
is a PTC protected version of this unit.
Agency Listings
UL Listed for Access Control Systems (UL294) CUL Listed - CSA Standard C22.2 No.205-M1983,
Signal Equipment. File# BP6714. CSFM - California State Fire Marshal Approved
File# 7315-1335:106. MEA - NYC Department of Buildings Approved. File# 18-98-E Vol 3.
Features/Specifications
Power Supply/Charger: 12VDC or 24VDC selectable output 6 amp of continuous supply current
115VAC 60Hz, 1.9 amp input Filtered and electronically regulated outputs.
Short circuit and thermal overload protection. Maximum charge current .7 amp.
Zero voltage drop upon transfer to battery backup. AC input and DC output LED indicators.
AC fail supervision (form "C" contact rated @ 1 amp 28VDC). Low battery and battery presence supervision
(form "C" contact rated @ 1 amp 28VDC). Lifetime Warranty
Access Power Controller:
Eight (8) Access Control System outputs
Eight (8) fuse protected Fail-Safe and/or Fail-Secure 12VDC or 24VDC power outputs.
Eight (8) fuse protected 12VDC or 24VDC auxiliary power outputs (unswitched).
Red LEDs indicate outputs are triggered (relays energized).
Eight (8) Access Control System trigger inputs
Eight (8) normally open (NO) inputs.
Eight (8) open collector inputs Any combination of the above
Fire Alarm Disconnect:Fire Alarm Disconnect (latching or non-latching) is individually
selectable for any or all of the eight (8) outputs.Normally open (NO) or normally closed (NC) dry contact input.
Polarity reversal input FACP signaling circuit. Fire Alarm trigger LED indicates that the Fire Alarm Disconnect has been activated.
Fire Alarm output relay for triggering auxiliary reporting devices (form "C" contact rated @ 1 amp 28VDC).
Lifetime Warranty
Enclosure
Accommodates up to two (2) 12VDC/12AH batteries
Dimensions:
15.5"H x 12"W x 4.5"D
1/2" and 3/4" combination knockouts
You must be logged in to request more information about products.
Login or Call
for Pricing.
Special Order Item.
ACCESS POWER CONTROLLER
This unit distributes and switches power to access
control systems and accessories. It converts a
115VAC 60Hz input into sixteen (16) independently
controlled 12VDC or 24VDC fuse protected outputs.
These power outputs can be converted to dry form
“C" contacts. Outputs are activated by an open collector
sink or normally open (NO) dry trigger input from
an Access Control System, Card Reader, Keypad,
Push Button, PIR, etc. The unit will route power to a
variety of access control hardware devices including:
Mag Locks, Electric Strikes, Magnetic Door Holders, etc.
Outputs will operate in both Fail-Safe and/or Fail-Secure
modes. The FACP Interface enables Emergency Egress,
Alarm Monitoring, or may be used to trigger other auxiliary
devices. The fire alarm disconnect feature is individually selectable
for any or all of the sixteen (16) outputs.
You must be logged in to request more information about products.
Login or Call
for Pricing.
Special Order Item.
24VDC 5 AMP BATTERY 4" H X 3.
You must be logged in to request more information about products.
Login or Call
for Pricing.
Special Order Item.
POWER SUPPLY 24VDC 4AMP
Recommended where an interface with a fire alarm system or battery backup is needed. The BPS linear power supply delivers more current than PSPs, and all BPS models are UL Class 2 listed, allowing for wire runs without the use of conduit from power supply to door.
Specification Sheet: MAG-BPS-24-4.pdf
You must be logged in to request more information about products.
Login or Call
for Pricing.
Special Order Item.
24VDC PWR SUPPLY MONITOR
You must be logged in to request more information about products.
Login or Call
for Pricing.
Special Order Item.